Special Cables • Temperature Measurement • Cable Harnessing

SABIX IBL 600 FRNC

Halogen-free, flame retardant Interbus-Loop cable

Marking for IBL 600 FRNC 66012853: SAB BRÖCKSKES · D-VIERSEN · IBL 600 FRNC 2 x 1,5 mm² and current meter marking CE

Marking for IBL 600 FRNC 66012853: SAB BRÖCKSKES · D-VIERSEN · IBL 600 FRNC 2 x 1,5 mm² and current meter marking CE

Application

SABIX IBL 600 FRNC is a halogen-free, flame retardant Interbus-Loop cable. This two-conductor Interbus-Loop cable is to be applied as a data transmission cable as well as for the supply of sensors. The three-conductor Interbus-Loop cables is applied for supply of actuators. These cables are also suitable for Interbus-Loop 2.

Outstanding features

  • EAC approval

Cable construction

Conductor

bare copper strands with reference to

IEC 60228, EN 60228, VDE 0295, class 5

Insulation

SABIX

Colour code

coloured acc. to HD 308 (VDE 0293 part 308);

green-yellow earth wire from 3 cores

Stranding

in layers

Sheath material

SABIX

Sheath colour

redlilac (RAL 4001)

Technical data

Peak operating voltage

max. 350 V

Testing voltage

1000 V

Min. bending radius

15 x d

Characteristic impedance

at 250 MHz - 10 MHz: for 2-core cabels 75Ω +/- 15%

Absence of harmful substances

acc. to RoHS directive of the European Union

Temperature range

fixed laying: -40/+85 °C

flexible application: -30/+85 °C

Halogen-free

acc. to DIN VDE 0472 part 815 + IEC 60754-1

Fire performance

no flame propagation acc. to IEC 60332-3 + EN 60332-3 Cat. C resp. D

Corrosiveness of conflagration gases

in compliance with IEC 60754-2 and EN 50267-2-2 + VDE 0482 part 267-2-2

- no development of corrosive conflagration gases

Smoke density:

acc. to IEC 61034 + EN 61034

Flexibility

good

Application in cable tracks

not recommended

Weather resistance

good

Dimensions

item no.outer-ø ± 5%copper figurecable weight ca.
660128532 x 1,50 mm²6,9 mm28,8 kg/km78 kg/km
660138533 x 1,50 mm²7,5 mm43,2 kg/km94 kg/km