Skip navigation

Special Cables • Temperature Measurement • Cable Harnessing

SABIX® A 146 S

Halogen-free wiring cable with improved fire performance 300/500 V

Marking for SABIX® A 146 S 81460150: SAB BRÖCKSKES · D-VIERSEN · SABIX® A 146 S 300/500 V 0,5 mm² CE

Marking for SABIX® A 146 S 81460150: SAB BRÖCKSKES · D-VIERSEN · SABIX® A 146 S 300/500 V 0,5 mm² CE

Application

SABIX® A 146 S is a halogen-free wiring cable with a voltage of 300/500 V. This single conductor is recommended for use in production of control cabinets, appliances and devices for communication technologies, household appliances, construction of generators and transformers, machine construction, and railway technologies.

Outstanding features

  • halogen-free
  • no flame propagation
  • flame retardant and self-extinguishing
  • very good stripping
  • flexible

Additional information

On request with tinned copper strands

* Colour code for single conductors:

01 = black

02 = blue
03 = brown
04 = grey
05 = yellow

06 = green
07 = violet
08 = white
16 = gentian blue
27 = green-yellow

Cable construction

Conductor

bare copper strands acc. to IEC 60228, VDE 0295, class 5

Insulation

SABIX®

Colour code

see table* additional informations

Technical data

Nominal voltage

Uo/U 300/500 V

Testing voltage

2000 V

Min. bending radius

7,5 x d

 

for one single bend:

5 x d

Temperature range

fixed laying: -30/+70 °C

flexible application: -20/+70 °C

Halogen-free

acc. to IEC 60754-1 + VDE 0482-754-1

Fire performance

no flame propagation acc. to IEC 60332-3-24 + VDE 0482-332-3-24 resp. IEC 60332-3-25 +

VDE 0482-332-3-25 cat. C resp. D, see chapter N „Technical Data“

Flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Corrosiveness of conflagration gases

in compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases

Smoke density

acc. to IEC 61034 + VDE 0482-1034

Flexibility

good

Absence of harmful substances

acc. to RoHS directive of the European Union

Dimensions

item no. nominal cross section largest single wire-ø outer-ø ± 5% copper figure cable weight ca.
8146 .. 50* 0,5 mm² 0,21 mm 2,1 mm 4,8 kg/km 10 kg/km
8146 .. 75* 0,75 mm² 0,21 mm 2,4 mm 7,2 kg/km 13 kg/km
8146 .. 80* 1 mm² 0,21 mm 2,5 mm 9,6 kg/km 15 kg/km