CC 600 blue (AWG 8 - AWG 1)
PVC control cable with numbered blue cores acc. to UL/CSA
Marking for CC 600 blue 02080805: SAB BRÖCKSKES · D-VIERSEN · CC 600 blue 8 AWG/5c0c 02080805 UL AWM Style 21216 90°C Oil 60°C 600V CSA AWM I/II A/B 90°C F 600V FT1 FT2 CE
Application
CC 600 blue is a PVC control cable with numbered blue cores and AWG 8 - AWG 1 and is on request available with metric conductor stranding and VDE- Reg. no. It is recommended for use in construction of service cabinets and control devices, electrical technology, installation and packaging techniques, construction of textile machines, wood working machines and machine tools.
Outstanding features
- UL and CSA approved
- high mechanical loading capacity
- oil resistant
- on request construction with metric conductor stranding and VDE-Reg. no.
Construction
Conductor | bare copper strands acc. to UL/CSA |
---|---|
Insulation | special PVC acc. to VDE and UL/CSA |
Colour code | blue cores with consecutive numbers acc. to EN 50334 + VDE 0293-334, green-yellow earth wire from 3 cores |
Stranding | in layers |
Sheath material | special oil resistant PVC acc. to VDE and UL/CSA |
Sheath colour | grey (RAL 7000) |
bare copper strands acc. to UL/CSA
special PVC acc. to VDE and UL/CSA
blue cores with consecutive numbers acc. to EN 50334 + VDE 0293-334,
green-yellow earth wire from 3 cores
in layers
special oil resistant PVC acc. to VDE and UL/CSA
grey (RAL 7000)
Technical data
Nominal voltage | DIN VDE: Uo/U 300/500 V UL/CSA: 600 V |
---|---|
Testing voltage | core/core 3000 V |
Min. bending radius | fixed laying: 4 x d flexible application: 6 x d |
Radiation resistance | 8 x 10^7 cJ/kg |
Temperature range | DIN VDE fixed laying: -40/+70 °C DIN VDE flexible application: +5/+70 °C UL/CSA fixed laying: up to +90°C UL/CSA flexible application: up to +90°C |
Fire performance | flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2, UL VW-1, CSA FT1, FT2 |
Oil resistance | very good - TM5 acc. to EN 50363-4-1 + VDE 0207-363-4-1, Oil 60 °C acc. to UL 758, Fuel Oil acc. to CSA-C 22.2 No. 210 |
Chem. resistance | see "Technical Data" - Chemical resistance |
Absence of harmful substances | acc. to RoHS directive of the European Union |
DIN VDE: Uo/U 300/500 V
UL/CSA: 600 V
core/core 3000 V
fixed laying: 4 x d
flexible application: 6 x d
8 x 10^7 cJ/kg
DIN VDE fixed laying: -40/+70 °C
DIN VDE flexible application: +5/+70 °C
UL/CSA fixed laying: up to +90°C
UL/CSA flexible application: up to +90°C
flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2,
UL VW-1, CSA FT1, FT2
very good - TM5 acc. to EN 50363-4-1 + VDE 0207-363-4-1,
Oil 60 °C acc. to UL 758, Fuel Oil acc. to CSA-C 22.2 No. 210
see "Technical Data" - Chemical resistance
acc. to RoHS directive of the European Union
Dimensions
item no. |
No. of cores x cross section |
Largest single wire-ø | Outer-ø ± 5% | Copper figure | Cable weight ≈ | |
---|---|---|---|---|---|---|
02080803 | 3 x 8 AWG | 0,41 mm | 15,3 mm | 253,4 kg/km | 449 kg/km | Send inquiry |
02080804 | 4 x 8 AWG | 0,41 mm | 17,0 mm | 337,9 kg/km | 570 kg/km | Send inquiry |
02080805 | 5 x 8 AWG | 0,41 mm | 18,9 mm | 422,4 kg/km | 696 kg/km | Send inquiry |
02080604 | 4 x 6 AWG | 0,41 mm | 20,9 mm | 541,4 kg/km | 845 kg/km | Send inquiry |
02080605 | 5 x 6 AWG | 0,41 mm | 23,6 mm | 676,8 kg/km | 969 kg/km | Send inquiry |
02080404 | 4 x 4 AWG | 0,41 mm | 25,6 mm | 844,8 kg/km | 1360 kg/km | Send inquiry |
02080208 | 4 x 2 AWG | 0,41 mm | 30,4 mm | 1344,0 kg/km | 2007 kg/km | Send inquiry |
02080104 | 4 x 1 AWG | 0,41 mm | 33,2 mm | 1651,2 kg/km | 2464 kg/km | Send inquiry |
cross section
wire-ø
Other dimensions and colours are possible on request.