SAB Kabel

A 20 L

PVC insulated cables, A 20 L · A 20-022 L · A 20 D

Application

NiCr-Ni cable (type K) with aluminium foil shielding and a PETP foil wrapping. The cable can be selected as a thermoelectric cable or as a compensating cable. NiCr-Ni cables can be used for a temperature measuring range from -25 C to +200 C. Further thermocouples can be freely selected.

Outstanding features

  • flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Additional information

We also manufacture compensating and extension cables colour coded to VDE 43714 – 06/79 and the basic values laid down in VDE 43710 which was withdrawn in April 1994.
 

Type:A 20 LA 20-022 LA 20 D
Conductor cross section:1,5 mm²0,22 mm²1,5 mm²
Outer diameter: approx. 6,6 mmapprox. 3,9 mmapprox. 6,4 mm
Weight/100m:approx. 5,5 kgapprox. 1,9 kgapprox. 5,5 kg

DIN 43710 / 43714 (not valid for type B*)
* Not standardized compensating cable for thermocouples type B with application temperatures up to 100 °C resp. 200 °C.
C = compensating cables · X = extension cables

 

Construction

Insulation

PVC, TI2 acc. to EN 50363-3 + VDE 0207-363-3

Stranding

2 cores together

Wrapping

PETP foil

bare copper earth wire 0,5 mm Ø

Screen

Alu-foil

Sheath material

PVC, TM2 acc. to EN 50363-4-1 + VDE 0207-363-4-1

Shape

round

Conductor construction

strand resp. wire

Insulation

PVC, TI2 acc. to EN 50363-3 + VDE 0207-363-3

Stranding

2 cores together

Wrapping

PETP foil

bare copper earth wire 0,5 mm Ø

Screen

Alu-foil

Sheath material

PVC, TM2 acc. to EN 50363-4-1 + VDE 0207-363-4-1

Shape

round

Conductor construction

strand resp. wire

Technical data

Min. bending radius

7,5 x d

Radiation resistance

8 x 10^7 cJ/kg

Temperature range of insulation

fixed laying: -40/+70°C

flexible application: +5/+70°C

Insulation resistance

> 1 M Ω x km

Fire performance

flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Absence of harmful substances

acc. to RoHS directive of the European Union

Min. bending radius

7,5 x d

Radiation resistance

8 x 10^7 cJ/kg

Temperature range of insulation

fixed laying: -40/+70°C

flexible application: +5/+70°C

Insulation resistance

> 1 M Ω x km

Fire performance

flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Highly flexible cables according to your special requirements

Family business for construction and production since 1947

Please send us your inquiry
+49 (0)2162 898-0
Monday to Thursday, 7.30–16.30
Friday, 07.30–15.00