SABIX® Lift
Lift control cable with sisal center as suspension unit
Application
SABIX® Lift is a halogen-free lift control cable with sisal cord as suspension unit. It gets used whenever there are highest safety requirements, especially in public buildings and institutions as, for example, department stores, hospitals, railway, and airport institutions, etc.
Outstanding features
- halogen-free
- long service life
- elevated economic efficiency
- flame retardant and self-extinguishing
Additional information
Possible on request!
- with total copper braiding
- with different conductor and sheath colours
Construction
Conductor | bare copper strands acc. to IEC 60228, VDE 0295, class 6 |
---|---|
Insulation | Spezial SABIX® |
Farbcodierung | black cores with consecutive numbers acc. to EN 50334 + VDE 0293-334 and a green-yellow earth wire |
Strain relief | sisal cord |
Stranding | sisal cord as core, optimized twisting of the conductors in layers |
Wrapping | non-woven tape on each layer with overlap wrapping |
Torsion protecting | special braid |
Sheath material | thermoplastic special elastome |
Sheath colour | black (RAL 9005) |
bare copper strands acc. to IEC 60228, VDE 0295, class 6
Spezial SABIX®
black cores with consecutive numbers acc. to EN 50334 + VDE 0293-334 and a green-yellow earth wire
sisal cord
sisal cord as core, optimized twisting of the conductors in layers
non-woven tape on each layer with overlap wrapping
special braid
thermoplastic special elastome
black (RAL 9005)
Technical data
Nominal voltage | Uo/U 300/500 V |
---|---|
Testing voltage | core/core 2000 V |
Min. bending radius | 15 x d |
Temperature range | fixed laying: -40/+90°C flexible application: -30/+90°C |
Halogen-free | acc. to IEC 60754-1 + VDE 0482-754-1 |
Fire performance | no flame propagation |
Suspended height | up to 60 m |
Absence of harmful substances | acc. to RoHS directive of the European Union |
Uo/U 300/500 V
core/core 2000 V
15 x d
fixed laying: -40/+90°C
flexible application: -30/+90°C
acc. to IEC 60754-1 + VDE 0482-754-1
no flame propagation
acc. to IEC 60332-3-24 + VDE 0482-332-3-24
resp. IEC 60332-3-25 + VDE 0482-332-3-25 category C resp. D
up to 60 m