SAB Kabel

A 13 L

Silicone (Besilen®) insulated cores with fibre-glass braiding

Application

Thermocouple cable type J with an oval shape and a parallel stranding. Moreover, this Thermocouple cable has a braiding of fibre-glass with tracer. The cable is available as compensating cable and thermocouple extension cable and it is suitable for various thermocouple types like, for instance, type T, type K, type J, and type R/S.

Additional information

Also available with cross-sections 1,0 mm², 0,75 mm², 0,5 mm² and 0,22 mm²!
 

Type:A 13 L
Conductor cross section:1,5 mm²
Outer diameter: approx. 3,0 x 5,5 mm
Weight/100m:approx. 3,8 kg

DIN 43710 / 43714 (not valid for type B*)
* Not standardized compensating cable for thermocouples type B with application temperatures up to 100 °C resp. 200 °C.
C = compensating cables · X = extension cables

Construction

Insulation

Besilen® EI2 acc. to EN 50363-1 + VDE 0207-363-1

Stranding

2 cores parallel

Braiding

fibre-glass with tracer

Shape

oval

Conductor construction

strand

For thermocouples

■ 1 x type T     ■ 1 x type J      ■ 1 x type K

■ 1 x type E     ■ 1 x type R/S     ■ 1 x type N

■ 1 x type L     ■ 1 x type U      ■ 1 x type B

Insulation

Besilen® EI2 acc. to EN 50363-1 + VDE 0207-363-1

Stranding

2 cores parallel

Braiding

fibre-glass with tracer

Shape

oval

Conductor construction

strand

For thermocouples

■ 1 x type T     ■ 1 x type J      ■ 1 x type K

■ 1 x type E     ■ 1 x type R/S     ■ 1 x type N

■ 1 x type L     ■ 1 x type U      ■ 1 x type B

Technical data

Min. bending radius

10 x d

Temperature range of insulation

fixed laying: -40/+180°C

flexible application: -25/+180°C

short-time use: +250°C

Insulation resistance

> 1 M Ω x km

Halogen-free

acc. to IEC 60754-1 + VDE 0482-754-1

Fire performance

flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Corrosiveness of conflagration gases

in compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases

Absence of harmful substances

acc. to RoHS directive of the European Union

Min. bending radius

10 x d

Temperature range of insulation

fixed laying: -40/+180°C

flexible application: -25/+180°C

short-time use: +250°C

Insulation resistance

> 1 M Ω x km

Halogen-free

acc. to IEC 60754-1 + VDE 0482-754-1

Fire performance

flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Corrosiveness of conflagration gases

in compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases

Highly flexible cables according to your special requirements

Family business for construction and production since 1947

Please send us your inquiry
+49 (0)2162 898-0
Monday to Thursday, 7.30–16.30
Friday, 07.30–15.00