Pt100 Table - Basic Values of Mineral Insulated Resistance Thermometers

Accuracy classes acc. to DIN EN 60751:2009-5

class                        validity range °Climit deviation* °C
 leaded resistorfilm resistor 
AA -50 up to +250   0 up to +150± (0,1 + 0,0017 [t])
A-100 up to +450-30 up to +300± (0,15 + 0,002 [t])
B-196 up to +600-50 up to +500± (0,3 + 0,005 [t])
C-196 up to +600-50 up to +600± (0,6 + 0,01 [t])
* [t] = value of temperature in °C without considering the sign.

For resistance thermometers that belong to the above context, the temperature coefficient a is defined as:α = (R100 - R0) : (100 x R0) = and has the numerical value 0,003 85°C-1 with: R100 is the resistance at 100°C and R0 is the resistance at 0°C. (for calculation purpose the exact value o0,003 850 55°C-1).

Limit deviations for PT 100 thermometers

abbreviation of RTD Pt 100 DIN EN 60751

RTD material platinum

application range -200 up to + 850 °C (class B)
ITS 90 resistance and permitted deviation
measuring temperaturebasic value                   allowed deviation
 class Aclass B
°CΩΩ°CΩ°C
-20018,52 ±0,24 ±0,55 ±0,56 ±1,30
-10060,26 ±0,14 ±0,35 ±0,32 ±0,80
0100,00  ±0,06±0,15±0,12±0,30
100138,51    ±0,13±0,35±0,30±0,80
200175,86 ±0,20 ±0,55 ±0,48 ±1,30
300212,05 ±0,27 ±0,75 ±0,64 ±1,80
400247,09 ±0,33 ±0,95 ±0,79 ±2,30
500280,98 ±0,38 ±1,15 ±0,93±2,80
600313,71 ±0,43 ±1,35 ±1,06 ±3,30
650329,64 ±0,46 ±1,45 ±1,13 ±3,60
700345,28--±1,17±3,80
800 375,70 --±1,28±4,30
850390,48--±1,34±4,60

 

for the term “basic values” see DIN 16160 part 5

Resistance thermometers with different accuracy classes and validity ranges as for example acc. to DIN EN 60751: 2009-5 (class AA) are available on request.

Do you have any questions about our products? Your direct line to our experts! Contact

Highly flexible cables according to your special requirements

Family business for construction and production since 1947

Please send us your inquiry
+49 (0)2162 898-0
Monday to Thursday, 7.30–16.30
Friday, 07.30–15.00